12 CONTROL SUB FUNCTIONS

(2) OPR retry operation when the workpiece is outside the range between the

upper and lower limits.

1) When the direction from the workpiece to the OP is the same as the "

Pr.44

OPR direction", a

normal machine OPR is carried out.

Pr. 44 OPR direction

Upper limit

Lower limit

Movement range

Machine OPR start

OP

Zero signal

Near-point dog

2) When the direction from the workpiece to the OP is the opposite direction from the "

Pr.44

OPR

direction", the operation carries out a deceleration stop when the near-point dog turns OFF, and
then carries out a machine OPR in the direction set in "

Pr.44

OPR direction".

Pr. 44 OPR direction

Near-point dog

Upper limit

Lower limit

Movement range

Machine OPR start

OP

Zero signal

Note) The above figures (a) and (b) are examples where "

Pr.44

OPR direction" is set to "0: Positive

direction". When "0: Positive direction" is set in

Pr.44

, check that the limit switch placed in the

OPR direction acts as the upper limit. When "1: Negative direction" is set in

Pr.44

, check that

the limit switch placed in the OPR direction acts as the lower limit. Incorrect wiring of these limit
switches may cause improper OPR retry operation. If any malfunction is identified, check and
correct "

Pr.6

Rotation direction setting" and the wiring.

Fig. 12.2 OPR retry operation from on limit (limit switch OFF)