When the "JOG start signal" is turned ON immediately after the stop signal
OFF (within 100ms)
When the "JOG start signal" is turned ON immediately after the stop signal OFF
(within 100ms), it will be ignored and the JOG operation will not be carried out.
ON
Axis stop signal
[Y4, Y5, Y6, Y7]
OFF
ON
OFF
100ms
A rise of JOG start signal is ignored.
Forward run JOG operation
Forward run JOG start signal
[Y8, YA, YC, YE]
Fig. 11.11 Operation when the JOG start signal is turned ON immediately after the stop signal OFF