11.4.3 Setting the required parameters for manual pulse generator operation

The "Parameters" must be set to carry out manual pulse generator operation.

The following table shows the setting items of the required parameters for carrying out

manual pulse generator operation. When only manual pulse generator operation will

be carried out, no parameters other than those shown below need to be set. (Use the

initial values or setting values within a range where no error occurs for trouble-free

operation.)

Setting item

Setting requirement

Factory-set initial value

(setting details)

Pr.1

Unit setting

3 (pulse)

Pr.2

No. of pulses per rotation (Ap) (Unit: pulse)

20000

Pr.3

Movement amount per rotation (Al) (Unit: pulse)

20000

Pr.4

Unit magnification (Am)

1 (1-fold)

Pr.5

Pulse output mode

1 (CW/CCW mode)

Pr.6

Rotation direction setting

0 (current value increases by

forward run pulse output)

Pr.11

Backlash compensation amount (Unit: pulse)

0

Pr.12

Software stroke limit upper limit value (Unit: pulse)

2147483647

Pr.13

Software stroke limit lower limit value (Unit: pulse)

–2147483648

Pr.14

Software stroke limit selection

0 (current feed value)

Pr.15

Software stroke limit valid/invalid setting

0 (valid)

Pr.17

Torque limit setting value (Unit: %)

300

Pr.22

Input signal logic selection

0 (Manual pulse generator

input is negative logic.)

Pr.23

Output signal logic selection

0 (Pulse output to drive unit is

negative logic.)

Param

e

ters

Pr.24

Manual pulse generator input selection

0 (4 times multiplication of A

phase/B phase)

: Setting always required.
: Set according to requirements (Leave set to the initial value when not used.)

REMARK

Parameter settings work in common for all control using the QD75. When carrying

out other control ("major positioning control", "high-level positioning control", "OPR

positioning control"), the respective setting items must also be matched and set.

Parameters are set for each axis. But

Pr.22

Manual pulse generator input logic

(b8),

Pr.24

is set only for axis 1. (The setting for axes 2,3, and 4 is ignored.)

Refer to Chapter 5 "Data Used for Positioning Control" for setting details.