12 - 7

MELSEC-Q

12 CONTROL SUB FUNCTIONS

[2] Precaution during control

(1) The following table shows whether the OPR retry function may be executed

by the "

Pr.43

OPR method".

Pr.43 OPR method

Execution status of OPR retry function

Near-point dog method

: Execution possible

Stopper method 1)

: Execution not possible

Stopper method 2)

: Execution not possible

Stopper method 3)

: Execution not possible

Count method 1)

: Execution possible

Count method 2)

: Execution possible

(2) Always establish upper/lower limit switches at the upper/lower limit positions

of the machine, and connect an QD75 module. If the OPR retry function is
used without hardware stroke limit switches, the motor will continue rotation
until a hardware stroke limit signal is detected.

(3) Always wire QD75 upper/lower limit switches even when the OPR function

is invalidated. Control cannot be carried out with the QD75 unless the wiring
is carried out.

(4) Do not carry out settings so that the drive unit power turns OFF by the

upper/lower limit switches connected to the QD75. If the drive unit power is
turned OFF, the OPR retry cannot be carried out.

[3] Setting the OPR retry function

To use the "OPR retry function", set the required details in the parameters shown

in the following table, and write them to the QD75.

When the parameters are set, the OPR retry function will be added to the

machine OPR control. The set details are validated at the rising edge (OFF

ON) of the PLC READY signal (Y0). Set "

Pr.57

Dwell time during OPR retry"

according to the user's requirements.

Setting item

Setting

value

Setting details

Factory-set
initial value

Pr.48

OPR retry

1

Set "1: Carry out OPR retry by limit switch".

0

Pr.57

Dwell time during
OPR retry

Set the deceleration stop time during OPR retry.
(Random value between 0 and 65535 (ms))

0

Refer to Section 5.2 "List of parameters" for setting details.

REMARK

Parameters are set for each axis.

It is recommended that the parameters be set whenever possible with GX

Configurator-QP. Execution by sequence program uses many sequence programs

and devices. The execution becomes complicated, and the scan times will

increase.