beautypg.com

Melsec-q, 12 control sub functions (2) after mode, 2] m code off request – MITSUBISHI ELECTRIC Mitsubishi Programmable Logic Controller QD75D User Manual

Page 543

background image

12 - 67

MELSEC-Q

12 CONTROL SUB FUNCTIONS

(2) AFTER mode

The M code ON signal (X4, X5, X6, X7) is turned ON at the positioning

completion, and the M code is stored in "

Md.25

Valid M code".

01

00

m1

m2

V

t

OFF

ON

OFF

OFF

ON

ON

0

0

1

Positioning start signal

BUSY signal

M code ON signal

Positioning

m1 and m2 indicate set M codes.

Md. 25 Valid M code

Da. 1 Operation pattern

Cd. 7 M code OFF request

[XC, XD, XE, XF]

[Y10, Y11, Y12, Y13]

[X4, X5, X6, X7]

Fig. 12.39 M code ON/OFF timing (AFTER mode)

[2] M code OFF request

When the M code ON signal (X4, X5, X6, X7) is ON, it must be turned OFF by

the sequence program.

To turn OFF the M code ON signal, set "1" (turn OFF the M code signal) in

" Cd.7 M code OFF request".

Buffer memory address

Setting item

Setting

value

Setting details

Axis

1

Axis

2

Axis

3

Axis

4

Cd.7

M code OFF
request

1

Set "1: Turn OFF the M code ON signal".

1504 1604 1704 1804

Refer to Section 5.7 "List of control data" for details on the setting details.

The next positioning data will be processed as follows if the M code ON signal is

not turned OFF. (The processing differs according to the " Da.1 Operation

pattern".)

Da.1

Operation pattern

Processing

00

Independent positioning control
(Positioning complete)

01

Continuous positioning control

The next positioning data will not be executed until the M code ON
signal is turned OFF.

11

Continuous path control

The next positioning data will be executed, but a warning "M code
ON signal ON start" (warning code: 503) will occur.