12 - 30

MELSEC-Q

12 CONTROL SUB FUNCTIONS

(5) During simultaneous start, a stroke limit check is carried out for the current

values of every axis to be started. Every axis will not start if an error occurs,
even if it only occurs in one axis.

[5] Setting the software stroke limit function

To use the "software stroke limit function", set the required values in the

parameters shown in the following table, and write them to the QD75.

The set details are validated at the rising edge (OFF ON) of the PLC READY

signal (Y0).

Setting item

Setting

value

Setting details

Factory-set
initial value

Pr.12

Software stroke
limit upper limit
value

Set the upper limit value of the moveable range.

2147483647

Pr.13

Software stroke
limit lower limit
value

Set the lower limit value of the moveable range.

–2147483648

Pr.14

Software stroke
limit selection

Set whether to use the "

Md.20

Current feed value" or

"

Md.21

Machine feed value" as the "current value".

0: Current feed

value

Pr.15

Software stroke
limit valid/invalid
setting

0 : V a l i d

Set whether the software stroke limit is validated or
invalidated during manual control (JOG operation,
Inching operation, manual pulse generator operation).

0: valid

Refer to Section 5.2 "List of parameters" for setting details.

[6] Invalidating the software stroke limit

To invalidate the software stroke limit, set the following parameters as shown,

and write them to the QD75.

Pr.12

Software stroke limit
upper limit value

=

Pr.13

Software stroke limit
lower limit value

(For manual operation, set "0: software stroke limit invalid" in the "

Pr.15

Software stroke limit valid/invalid setting".)

The set details are validated at the rising edge (OFF ON) of the PLC READY

signal (Y0).

When the unit is "degree", the software stroke limit check is not performed during

speed control (including speed control in speed-position switching control or

position-speed switching control) or during manual control, independently of the

values set in

Pr.12

,

Pr.13

and

Pr.15

.

REMARK

Parameters are set for each axis.

It is recommended that the parameters be set whenever possible with GX

Configurator-QP. Execution by sequence program uses many sequence programs

and devices. The execution becomes complicated, and the scan times will

increase.