12 - 62

MELSEC-Q

12 CONTROL SUB FUNCTIONS

[6] Precautions during control

(1) When step operation is carried out using interpolation control positioning

data, the step function settings are carried out for the reference axis.

(2) When the step valid flag is ON, the step operation will start from the

beginning if the positioning start signal is turned ON while "

Md.26

Axis

operation status" is "step standing by". (The step operation will be carried

out from the positioning data set in " Cd.3 Positioning start No.".)

[7] Step function settings

To use the "step function", write the data shown in the following table to the

QD75 using the sequence program. Refer to section [4] "Using the step

operation" for the timing of the settings.

The set details are validated when written to the QD75.

Buffer memory address

Setting item

Setting

value

Setting details

Axis

1

Axis

2

Axis

3

Axis

4

Cd.34

Step mode

Set "0: Deceleration unit step" or "1: Data No.
unit step".

1544 1644 1744 1844

Cd.35

Step valid flag

1

Set "1: Carry out step operation".

1545 1645 1745 1845

Cd.36

Step start
information

Set "1: Step continue", depending on the stop
status.

1546 1646 1746 1846

Refer to Section 5.7 "List of control data" for details on the setting details.