Power requirements – Nortel Networks 1000 User Manual

Page 125

background image

Electrical specifications

125

Table 50
OPS analog line card - electrical characteristics (cont’d.)

Characteristic

Specification

Line leakage

30k ohms, tip-to-ring, tip-to-ground,

ring-to-ground

AC induction rejection

10 V rms, tip-to-ring, tip-to-ground,
ring-to-ground

Table 50 "OPS analog line card - electrical characteristics" (page 124)

lists

the electrical characteristics of OPS analog line card line interface units.

Power requirements

Table 51 "OPS analog line card - power requirements" (page 125)

shows

the maximum power consumed by the card from each system power
supply.

Table 51
OPS analog line card - power requirements

Voltage

Tolerance

Current (max.)

±15.0 V dc

± 5%

150 mA

+8.5 V dc

± 2%

200 mA

+5.0 V dc

± 5%

100 mA

–48.0 V dc

± 5%

350 mA

The +8.5 V dc input is regulated down to +5 V dc for use by the digital
logic circuits. All other power to the card is used by the line interface
circuits.

The +8.5 V dc input is regulated down to + 5 V dc for use by the digital
logic circuits. All other power to the card is used by the line interface
circuits.

The +8.5 V dc input is regulated down to +5 V dc for use by the digital
logic circuits. All other power to the card is used by the line interface
circuits. The ±15.0 V dc inputs to the card are used to power the analog
circuits. The +5 V dc from the module power supply is used for the analog
hybrid. The

–48.0 V dc input is for the telephone battery. Ringing power for telephones
is 86 Vrms ac at 20 Hz on –48 V dc. The Rsync signal is used to switch
the 20 Hz ringing on and off at the zero cross-over point to lengthen the
life of the switching circuits.

Nortel Communication Server 1000

Circuit Card Reference

NN43001-311

02.06

Standard

27 August 2008

Copyright © 2003-2008 Nortel Networks

.