System i/o functions – Rockwell Automation 5370-CVIM2 Module User Manual
Page 478
![background image](/manuals/580351/478/background.png)
5
Chapter
Chapter 9
Discrete I/O Assignments
9–15
Output Status from Various +/– and Force Selections
Table 9.1 shows the output status (activated or deactivated) for each
combination of inspection results (true and false) and corresponding settings
of “
+/–
” (
Pos
and
Neg
) and “
Force
” (
No
,
On
, and
Off
).
Table 9.1 Output States from Various Inv and Force Selections
Inspection Results
+/– Selection
Force Selections
*Output Status
Any
Pos
Off
Deactivated
Any
Pos
On
Activated
Any
Neg
Off
Activated
Any
Neg
On
Deactivated
False
Pos
No
Deactivated
True
Pos
No
Activated
False
Neg
No
Activated
True
Neg
No
Deactivated
*When the CVIM2 system is offline, all outputs (except the strobe output) are deactivated.
System I/O
is the second of the four
Discrete I/O
devices. You can select it
as shown in Figure 9.10 (page 9–16).
When the
System I/O
format is on the monitor screen, all 16 rows of the
table are available for input or output signal assignments. The inputs and
outputs assigned in this panel are routed to the
System I/O
connector on the
CVIM2 front panel.
Note that initially all of the rows are designated as outputs, “
Out 0
” to
“
Out1
5.” To change any row to an input signal, just pick one of the “out”
boxes. When you do, the “out” box toggles to become an “in” box. Thus,
“
Out 0
” toggles to “
In 0
,” for example.
NOTE: Triggers should be assigned only to inputs 0 and 1 on the
Module
I/O
panel and inputs 0 to 3 on the
System I/O
panel. Other inputs should not
normally be assigned to these inputs. (See Discrete Inputs: Interrupt
Processing vs Poll Processing on page 9–3 for details.)
For information about selecting input and output signals, refer to the Module
I/O Functions section on page 9–4.
System I/O Functions