Rockwell Automation 5370-CVIM2 Module User Manual
Page 469
Chapter 9
Discrete I/O Assignments
9–6
You can assign more than one input signal from the
Input Signals
list to a
single discrete I/O input. For example, you could assign both
Toolset
1.Trigger
and
Toolset 2.Trigger
in Figure 9.3 (page Figure 9.3) to discrete
input “
In 0
” in the
Module I/O
editor.
You can assign a trigger input signal to only one discrete I/O input. For
example, if you assign
Toolset 1.Trigger
to discrete input “
In 0
,” as shown
in Figure 9.3, and then assign that same input signal to another discrete I/O
input, it will be removed from “
In0
.”
To remove a trigger input signal from the discrete I/O editor, pick its name in
the
Inputs Signals
list, then pick the
button.
Bank Switch Input Selection
The
Bank Switch
input function is used to activate either cameras 1, 2, and
3 or cameras 4, 5, and 6. (Normally, this function should be assigned only to
the
System I/O
panel, as an input, on one of lines 4 through 15. Lines 0
through 3 on the
System I/O
panel, and lines 0 and 1 on the
Module I/O
panel should be reserved for trigger inputs. See Discrete Inputs: Interrupt
Processing vs Poll Processing on page 9–3 for details.)
DV Reset Input Selection
The
DV Reset
(data valid reset) input function is intended for operations in
which the CVIM2 system is connected to an Allen–Bradley PLC
through
the
Remote I/O
front panel connection.
The
DV Reset
function is assigned as an output from the PLC in the
Remote I/O
panel (an input to the CVIM2 system). It is one of the
“handshaking” signals used between the two systems. For details about its
use, refer to the CVIM2 Communications Reference Manual.
In1 – In8 Input Selections
Input selections
In1
through
In4
(or
In1
through
In8
if the “
tsin
”
environment variable is set to 08) can be configured as general purpose input
signals that can be used in math tool formulas and “
Condition
” selections in
the toolset edit panel. In a math tool formula, these inputs return a logic “1”
when active, and a logic “0” when inactive. In a
Condition
selection, these
inputs, when active, enable the corresponding tool to execute, and when
inactive, prevent a tool from executing.