Configuration editor panel – Rockwell Automation 5370-CVIM2 Module User Manual
Page 92
Chapter 4
Inspection Configuration
4–6
the
Config
field. You can use this name, if it is appropriate for your
application, or you can enter a different name.
When the appropriate
Acq. Config
file name is in the keyboard, and you
pick the
key, that file name appears in the scrolling list, as shown for
the
Config
file name in Figure 4.4 (page 4–4). (Note that the new name also
appears in the
Acq. Config
field since it is currently highlighted in the list.)
If you exit the
Config Files
panel at this time by picking the
button,
the following message will appear briefly . . .
Configuration save complete
. . . after which the system will exit to the main menu bar.
At this point, a minimum “configuration” has been named, and you can now
pick the
Configuration Editor
panel from
Editor
in the main menu bar, as
described in the next section, Configuration Editor Panel.
To enter the
Discrete I/O
and/or
Message
file names before exiting the
Config Files
panel, use the procedure described above to enter those file
names.
The main purpose of the
Configuration Editor
panel is to designate the
inspection parameters and inspection tool sets for each toolset in a
configuration file.
NOTE: Before you can select the
Configuration Editor
panel, you must
first create or select a configuration file with a valid
Config
file name, as
described in the preceding section, Configuration Process; otherwise, the
following message will appear when you attempt to select the
Configuration
Editor
panel:
If this message appears, you must pick the
button, then select the
Config
Files
panel (see Figure 4.2, page 4–2) to set up (and select) at least one
configuration before proceeding.
Configuration Editor Panel