beautypg.com

Station setup calculations panels, Values tab, Fullscale tab – MTS Series 793 User Manual

Page 382

background image

//output0 = rsp/100.0;
//output0 = IIR("Left Front Command" , iir);

Example script for FIR filters

int fir[6];
real fPass, fStop, dPass, dStop;
int rsp;
int type;
function int OnInitialize() {

fPass = 20.0;
fStop = 90.0;
dPass = 0.001;
dStop = 0.01;
type = 0;
rsp = FIRLP(fir, 120, fPass, fStop, dPass, dStop);

}
//output0 = rsp/100.0;
output0 = FIR("Left Front Command" , fir);

Station Setup Calculations Panels

Values Tab

This panel displays the current values of all calculated output signals.

Access

Display menu > Station Setup > Station Setup window > navigation pane > Calculations > Calculated Outputs
> Values tab

Warning:

For systems with calculated outputs and multiple independent HSMs, turning on only one HSM
can result in unexpected or exaggerated actuator motion.

Unexpected or exaggerated actuator motion can injure anyone in its path.

For these systems, always use the All Off, All Low, and All High buttons on the Station Controls
panel for hydraulic control.

Fullscale Tab

This tab displays the Fullscale Min and Max ranges for each calculated output signal.

Access

Display menu > Station Setup > Station Setup window > navigation pane > Calculations > Calculated Outputs
> Fullscale tab

382 MTS Series 793 Control Software

Calculated Signals