Peak/Valley Compensators Properties
PVC Tab Settings
Description
Item
Sets how quickly compensation values are applied to converge the
feedback and command signals.
Convergence Rate
Determines how much the feedback signal must change, as a percentage
of its peak-to-peak value, before a peak or valley is detected.
Sensitivity
Hold—Continues to use current values but stops adapting new values.
Adaptation State
Resume—Adapts and continuously updates compensation values.
Clears acquired compensation values and restarts the adaptation process.
Reset
Clicking Reset with compensation applied may produce a spike in the
feedback signal. Read the Warning that follows this table.
Warning:
Clicking Reset (or Reset All) in this tab with hydraulic pressure on can result in unexpected
actuator movement.
A moving actuator can injure anyone in its path.
Always clear the actuator area before clicking Reset.
How to Set Up PVC Compensators
1. Select an access level of Tuning.
2. In the Station Setup window navigation pane, locate and select the Channels control mode that requires
compensation.
3.
In the Station Setup window, click
.
4. In the Compensators panel, click the PVC tab.
Warning:
Changes in compensation values made with hydraulic pressure on can result in unexpected
actuator movement.
A moving actuator can injure anyone in its path.
Always clear the actuator area before changing compensation values.
MTS Series 793 Control Software 249