Callout

The Anticipation value (dX) in this example is 0.05859. Enter
this value for the Anticipation control on the AIC page as
0.06.

1

Points to mark on the feedback to determine Anticipation
(dX).

2

i) Enter this value on the Anticipation slider in the AIC page of the Compensators window.

j) To save the tuning values, go to the Station Manager window’s File menu and select Save Parameters.

4. Determine Impulse Response.

a) On the same scope trace, mark the point in feedback in which feedback begins gaining amplitude, and

then mark another point as the feedback has reached it max amplitude and is beyond any ringing (is
totally flat). The x-axis delta of these two points is the Impulse Response.

260 MTS Series 793 Control Software