Handset options tab – MTS Series 793 User Manual
Page 135
Description
Item
If hydraulic pressure is present at the station’s HSM when you
disable the integrator, a message will appear cautioning about
unexpected actuator movement.
Holding—maintains the current integrator value.
•
Auto-High (default)—turns on the integrator when system
hydraulics are set to High.
•
Auto-Low—turns on the integrator when system hydraulics
are set to Low.
From any integrator mode, the integrator will turn off when system
hydraulics are turned off.
When switching from automatic integration to manual integration,
the state the manual control assumes is a function of the HSM
state when the switch occurs:
Manual Integrator
Mode
Current Integrator Stator
HSM State
Enabled
Auto-Low
Low
Holding
Auto-High
Low
Enabled
Auto-Low or Auto-High
High
Enabled
Auto-Low or Auto-High
Off
System Controls (All Stations)
Note:
You must be at the Configuration access level to change
this control. Also, this control will be disabled if no remote
setpoint channels exist in the current station.
Use the Setpoint Enable on RSC control to enable the setpoint
control on the Remote Station Controller.
When Manual Control is enabled on the RSC, this check box is
disabled. You must disable manual control on the RSC to select
this check box.
Handset Options Tab
This tab allows you to define and change handset properties.
Access
Tools menu > Station Options > Station Options window > Handset Options tab.
Description
Item
Choose the handset from the submenu.
Handset
MTS Series 793 Control Software 135
Station Manager Application