Troubleshooting Outline
MotionSuite™ MP940 Machine Controller Reference Manual
9-4
Content of LED Display
The display content and countermeasure methods for the LEDs displaying
the MP940 operation status and error content are shown below.
Note: In the display light LED ×: OFF;
:ON; §:Flash; —:Undefined
Type
Display Light Name
Display Content
Countermeasure
RDY RUN
ALM
BAT
Nor-
mal
×
×
×
Hardware Reset State
The CPU normally starts within 1 second. If
this state continues, there is a software error/
hardware fault. Execute system error coun-
termeasures.
×
×
×
×
Initial Execution
×
×
×
User Program Stopped
(online stop mode)
When a STOP operation is executed by
MotionWorks
TM
. This state results when the
RUN switch is turned OFF.
×
×
User Program Executing
Normally
This state results during normal execution.
Error
×
×
Major Fault Generation
—
×
×
Program Memory
Initialization Complete
Scan Time Setting
Error
Execute the program memory clear operation
in the MotionWorks
TM
system definition
screen. A hardware failure is suspected if the
system does not recover.
×
×
§
×
Hardware Error
Number of Flashes
2: RAM Diagnostic Error
3: ROM Diagnostic Error
4: CPU Function Diag-
nostic Error
5: FPU Function Diag-
nostic Error
Hardware fault. Execute system error counter-
measures.
Warn-
ing
—
—
—
Battery Alarm
Replace the battery.
§
Operation Error
—
I/O Error
—
Invalid Assignment Error —
Report to system register
(no LED display)
MotionWorks
TM
Connection Data
See the System Status Display table.
Hardware Status
(momentary stop, RUN/
STOP, testing mode,
etc.)
See the System Status Display table.