Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

87

Drive Installation

Chapter 2

Grounding Practices

The purpose of grounding is to:

provide for the safety of personnel

limit dangerous voltages on exposed parts with respect to ground

facilitate proper overcurrent device operation under ground fault
conditions, and

provide for electrical interference suppression

Refer to the grounding diagrams that follow for ground connections. The drive’s
main ground bus must be connected to the system ground. This ground bus is the
common ground point for all grounds internal to the drive.

Figure 70 - Ground Connection Diagram with Isolation Transformer

Figure 71 - Ground Connection Diagram with Line Reactor

Each power feeder from the substation transformer to the drive must be provided
with properly sized ground cables. Utilizing the conduit or cable armor as a
ground on its own is not adequate.

Note that if a drive isolation transformer is used, the WYE secondary neutral
point should not be grounded.

Each AC motor frame must be bonded to grounded building steel within 6 m
(20 feet) of its location and tied to the drive’s ground bus via ground wires within

IMPORTANT

Generally, the means used for external grounding of equipment should be in
accordance with the Canadian Electrical Code (CEC), C22.1 or the National
Electrical Code (NEC), NFPA 70 and applicable local codes.

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTER