beautypg.com

System programming, Advanced screen operations, Communications statistics – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 158: System programming advanced screen operations

background image

158

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 3

Operator Interface

Pressing the [F5] key may restart an aborted download or one that failed. To
select or enter a different filename, press the [F7] key.

System Programming

The firmware for the complete drive system may be updated via serial port #2 on
the Customer Interface Board. Pressing the [F9] key from the transfer screen will
place the drive system into download mode.

Advanced Screen Operations

A number of advanced functions have been incorporated into the operator
interface. These operations are not required to operate the drive. They are meant
as service tools for trained technicians and have been included here only for
completeness.

All operations are accessed via a two key sequence.

Communications Statistics

The screen, depicted in

Figure 169

shows statistics involving the serial

communications between the operator interface and the drive as well as the
contents of the transmit and receive buffers. It is called from any screen (except
the PRINTER screen), by pressing the [F10] key and the [cursor down] key at
the same time.

Figure 169 - Communications Statistics & Buffer

The ERRORS show the number of occurrences of a particular error since the last
time the counters were reset.

• Parity

: number of parity errors in characters received.

• Framing

: number of framing errors in the characters received.

• Overrun

: number of characters received that were not read prior to

accepting the next character.

• Resends

: number of times the operator interface had to resend data due to

a NACK being sent by the drive.

• Timeouts

: number of times the operator interface did not receive data

from the drive within a specified time period.