Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

259

Commissioning

Chapter 4

Sample waveforms of DC Test recorded on 18 Pulse Drive
Idc Cmd Test = 0.5pu [Ch1- Vdcr1 (yellow) Ch2 – Idc1 (blue) at ACB test points]

Load Test

After autotuning of the drive, run the motor on load and capture the following
waveforms at 50% load and at 100% load. If the system is not ready for 100% load
test, then capture the waveforms at the max load you are allowed to run the drive
at. Also, print variables at 50% and 100% load points. Before printing variables
make sure the drive Access Level is at SERVICE.

1.

Capture line voltage & current waveforms at ACB test points “V2uv” &
“I2u”.

2.

Label the waveforms as “V2uv” and “I2u”.

3.

Capture motor voltage & current waveforms at ACB test points “Vuv” &
“Iu”

4.

Label the waveforms as “Vuv” and “Iu”.

5.

Save the worksheet as “Line and Load Voltage and Current Waveforms at
1048 rpm, 31 A”, for example.

Table 16 - Oscilloscope Setting

Oscilloscope

Time Base

Waveform

Test-Point

Waveform
Label

Sheet Name

Ch. 1

10ms/div.

Line Voltage

V2uv

V2uv

[see above]

Ch. 2

Line Current

I2u

I2u

Ch. 3

Motor Voltage

Vuv

Vuv

Ch. 4

Motor Current

Iu

Iu