Component Definition and Maintenance

Chapter 5

Fluid Conductivity

An in-line conductivity sensor (XS) (

Figure 282

) measures the fluid

conductivity. The sensor sends a signal to a meter mounted on the pump cabinet
door. Two conductivity switches are part of the meter. They are set at
conductivity of 1 μS/cm

3

for the annunciation warning and 2 μS/cm

3

for the trip

value.

Change the deionization cartridge when the conductivity rises to the warning
level.

Figure 282 - Temperature and Conductivity Sensors

Temperature Sensor

This temperature sensor (TS1), shown in

Figure 282

, triggers the drive to shut

down when the fluid temperature entering the converter cabinet is too high. This
situation could occur if the air cooling of the heat exchanger is cut off due to fan
failure, plugging of the air paths, or failure of the thermostatic valve.

The following are the temperature values for alarm and trip signal:

1.

When coolant temperature is greater than 48 °C (120 °F), an alarm signal
is initiated. It can only be reset when temperature reaches 38 °C (100 °F).

Conductivity Sensor x5

Strainer STR1

V6 Fill/Drain Valve

Temperature Sensor TS1