Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

359

Component Definition and Maintenance

Chapter 5

ohm input impedance. Regardless of input configuration, each input is
individually isolated to ± 100V DC or 70V RMS AC.

A block diagram of the receiver is shown in

Figure 295

.

Figure 295 - Process Loop Receiver Block Diagram

Non-Isolated Process Outputs

The drive supplies four non-isolated -10/0/+10 V outputs for customer use.
These outputs can drive loads with impedances as low as 600 ohms. These
outputs are all referenced to the Drive AGND and therefore should be isolated if
they are required to drive outside the PowerFlex “C” frame enclosure.

Figure 296 - Non-Isolated Configurable Analog Outputs on ACB

4,8,12

3,7,11

ŀ/#

X1

U1

FPGA

DSP

1

st

I/P pins

3

rd

I/P pins

2

nd

I/P pins

A/D

Buffer

1,5,9

2,6,10

Isolation Amplifier

+

+

-

-

A/D

DSP

FPGA

27,31,35,39

Analog
Output

25,29,33,37

28,32,36,40

IFM Pin#