Synchronous transfer – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 261
![background image](/manuals/580441/261/background.png)
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
261
Commissioning
Chapter 4
Synchronous Transfer
When commissioning a drive employing synchronous transfer, the following
waveforms should be captured and submitted with the commissioning package.
Refer to the “Synchronous Transfer Commissioning Guidelines” for a detailed
commissioning procedure.
While measuring the bypass (BP) contactor closing time:
•
Capture 120V bypass close command from the BP Contactor Close
output ( J1-12) at the ACB (refer to electrical drawing for specific wire/
terminal number).
•
Capture the 9V signal across the bypass contactor vacuum bottles (refer to
the tech note PowerFlex 7000_GEN-78 for details).
•
Label the waveforms as “BP_Close_Cmd” and “Actual_Closure”.
•
Save the worksheet as “Bypass Contactor Close Delay”.
Table 17 - Oscilloscope Setting
Figure 217 - Sample Waveforms
Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)
Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor vacuum bottles)
While simulating a synchronous transfer to determine the best lead angle:
•
Make sure the Diagnostic Trend has been setup and is armed.
•
Capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.
Oscilloscope
Time Base
Waveform
Test-Point
Waveform Label
Ch. 1
25ms/div.
BP Contactor Close
Command
BP Contactor Close
Cmd
BP_Close_Cmd
Ch. 2
Actual Closure of BP
Across 2K-Ohm
resistor connected in
series with 9V
battery
Actual_Closure