Commissioning

Chapter 4

Synchronous Transfer

When commissioning a drive employing synchronous transfer, the following
waveforms should be captured and submitted with the commissioning package.
Refer to the “Synchronous Transfer Commissioning Guidelines” for a detailed
commissioning procedure.

While measuring the bypass (BP) contactor closing time:

Capture 120V bypass close command from the BP Contactor Close
output ( J1-12) at the ACB (refer to electrical drawing for specific wire/
terminal number).

Capture the 9V signal across the bypass contactor vacuum bottles (refer to
the tech note PowerFlex 7000_GEN-78 for details).

Label the waveforms as “BP_Close_Cmd” and “Actual_Closure”.

Save the worksheet as “Bypass Contactor Close Delay”.

Table 17 - Oscilloscope Setting

Figure 217 - Sample Waveforms

Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)
Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor vacuum bottles)

While simulating a synchronous transfer to determine the best lead angle:

Make sure the Diagnostic Trend has been setup and is armed.

Capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.

Oscilloscope

Time Base

Waveform

Test-Point

Waveform Label

Ch. 1

25ms/div.

BP Contactor Close
Command

BP Contactor Close
Cmd

BP_Close_Cmd

Ch. 2

Actual Closure of BP

Across 2K-Ohm
resistor connected in
series with 9V
battery

Actual_Closure