beautypg.com

Connect the sections, Tools required (not supplied), Install cpvc piping splices – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 39

background image

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

39

Drive Installation

Chapter 2

Connect the Sections

Field connect the following:

CPVC pipe splices – 2 pieces

Power Bus Splice Kit – 4 pieces

Ground Bus Splice – 1 piece

Control Wiring

Tools Required (not supplied)

Adjustable or socket wrenches for 6-, 10-, 12-mm and 5/8" bolt and nut
hardware

Strap wrench for tightening CPVC unions

Screwdriver assortment

Cable ties

Wire cutters

Install CPVC Piping Splices

Open doors of capacitor cabinet (Cabinet #5) next to DC Link Choke
cabinet (Cabinet #6). Refer to

Figure 16

.

Remove capacitor from position #3, if installed (not all configurations
have a capacitor in this location). It is not necessary to remove capacitor
from position #2.

WARNING: Heavy Magnetic DC Link Chokes up to 4600 kg (10,000 lb) are
shipped inside DC Link Choke cabinet. Professional Millwright/Rigging
contractors are required for safe final placement of Drive sections.

ATTENTION: Capacitors weigh up to 100 kg (220 lb). Use two people to
remove the unit from the structure.