368

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 5

Component Definition and Maintenance

Table 27 - Status of U6 Display

External Input/Output Board Replacement

To replace the External Input/Output Boards:

1.

Ensure that all medium voltage and control voltage power to the drive is
isolated and locked out.

2.

Note and Mark the location and orientation of all the plugs, cables, and
connectors into the XIO board. Use the electrical drawing as a reference.

3.

Using your static strap, disconnect all of the connections.

4.

Remove the XIO board assembly from the low voltage control cabinet.
The XIO board mounts on a DIN rail, so a special 3-piece assembly is used
to secure the board. The assembly does not come with the new board, so
the old board needs to be removed from the assembly and the new board
installed in its place.

5.

Install the new XIO board assembly in the low voltage control cabinet.

6.

Reconnect all connections and verify the locations.

7.

Apply Low Voltage power and complete a System Test and Medium
Voltage tests to ensure the new board functions properly.

LED Status

Description

Solid Red

Board Failure

Alternate Flashing of Red and Green

No Communication Available to ACB board (Normal at
Power on, during firmware download and with
unprogrammed drive)

Display

Description

Explanation

No valid address found

More than 6 XIO cards on network
IO cable failure
IO card failure
CB failure

0

Card in “Master” mode

Rockwell Use Only
Remove connection to J3 and recycle power

1 – 6

Valid address

Normal

Decimal point ON

Indicates network activity

Normal

Decimal point OFF

No activity on the network

Normal at Power on, during firmware download

and with unprogrammed drive