Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 417
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
417
Catalog Number Explanation
Appendix A
Screw type, loaded
CT
200
100
100
Contact factory
Yes
DRAG LINE
CT
100
200
200
Contact factory
Yes
EXTRUDERS
(rubber or plastic)
CT
150
150
100
Contact factory
Yes
FANS (centrifugal, ambient)
Damper closed
VT
25
60
50
Normal
No
Damper open
VT
25
110
100
Normal
No
FANS (centrifugal, hot gases)
Damper closed
VT
25
60
100
Normal
No
Damper open
VT
25
200
175
Contact factory
No
FANS
(propeller, axial flow)
VT
40
110
100
Normal
No
GRINDING MILL
(Ball/Sag Mill)
CT
175
180
100
Contact factory
Yes
HOISTS
CT
100
200
200
Contact factory
Yes
KILNS (rotary, loaded)
CT
250
125
125
Contact factory
Yes
MIXERS
Chemical
CT
175
75
100
Contact factory
Yes
Liquid
CT
100
100
100
Heavy
Yes
Slurry
CT
150
125
100
Heavy
Yes
Solids
CT
175
125
175
Contact factory
Yes
PULPER
VT
40
100
150
Contact factory
No
PUMPS
Centrifugal, discharge open
VT
40
100
100
Normal
No
Oil field Flywheel
CT
150
200
200
Contact Factory
Yes
Propeller
VT
40
100
100
Normal
No
Fan Pump
VT
40
100
100
Norma
No
Reciprocating / Positive
Displacement
CT
175
30
175
Contact factory
Yes
Screw type, started dry
VT
75
30
100
Normal
No
Screw type, primed, discharge
open
CT
150
100
1000
Heavy
Yes
Slurry handling, discharge
open
CT
150
100
100
Heavy
Yes
Turbine, Centrifugal, deep-
well
VT
50
100
100
Normal
No
Vane-type, positive
displacement
CT
150
150
175
Contact factory
Yes
SEPARATORS, AIR
(fan type)
VT
40
100
100
Normal
No
(1) PowerFlex 7000 “A” Frame suitable only for normal service duty rating.
Table 33 - Typical Application Load Torque Profiles (Continued)
(1)
Application
Load Torque
Profile
Load Torque as Percent of Full-Load Drive Torque
Required Drive
Service Duty Rating
Encoder Required for
Extra Starting
Torque?
Break-away
Accelerating
Peak Running