Harmonic analysis (required for afe drives only), Summary – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 257

background image

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

257

Commissioning

Chapter 4

Harmonic Analysis
(required for AFE drives only)

Measure the harmonic (resonance) levels at the input to the drive.

Summary:

Drive input contactor should be closed. If the drive input contactor
configuration is set to NOT RUNNING, you will have to temporarily
change it to ALL FAULTS.

Ensure that the drive is not running when capturing these waveforms.

Capture line voltage at ACB test point “V2uv” and line current at ACB
test point “I2u”.

Label the waveforms as “V2uv”, and “I2u”.

Save the worksheet as “Harmonics (Drive Not Running)”.

Table 14 - Oscilloscope Setting

Figure 214 - Sample Waveforms

Sample waveforms captured on SCBL test points under Drive Not Running
Condition [Ch1: V2uv (red), Ch2: I2u (yellow)]

TIP

Please refer to tech note PowerFlex 7000_GEN-15 to compare the waveforms
for harmonic distortion. If you notice considerable distortion in the waveforms
then you MUST send those waveforms to MV Support via e-mail at
[email protected] and then call at 519-740-4790
(option 1) to discuss the issue and action plan. During after-hours, you can call
MV Support pager (Pager # 519-654-5616) to talk with MV Tech Support
Specialist. If you are out side North America, then call at 1-440-646-3434 and
ask for MV Tech Support.

Oscilloscope

Time Base

Waveform

Test-Point

Waveform
Label

Sheet Name

Ch. 1

10ms/div.

Line Voltage

V2uv

V2uv

Harmonics
(Drive Not
Running)

Ch. 2

Line Current

I2u

I2u