Overview of Drive
Chapter 1
IEEE 519 Harmonic Guidelines
(6)
IEEE 519 - 1992 Compliant
VFD Noise Level
< 85 dB (A)) per OSHA Standard 3074
Regenerative Braking Capability
Inherent – No Additional Hardware or Software Required
Flying Start Capability
Yes – Able to Start into and Control a Spinning Load in Forward or Reverse
Direction
Operator Interface
10” Color Touchscreen – Cat# 2711P-T10C4A9 (VAC)
Built-in PDF viewer
Redesigned PanelView Plus 6 Logic Module with 512 Mb of memory
Languages
English, French, Spanish, Portuguese, German, Chinese, Italian, Russian, and
Polish
Control Power
220/240V or 110/120V, Single phase - 50/60 Hz (20 A)
External I/O
16 Digital Inputs, 16 Digital Outputs
External Input Ratings
50…60 Hz AC or DC
120…240V – 1 mA
External Output Ratings
50…60 Hz AC or DC
30…260V – 1 A
Analog Inputs
Three Isolated, 4…20 mA or 0…10V (250 Ω)
Analog Resolution
Analog input 12 Bit (4…20 mA)
Internal parameter 32 Bit resolution
Serial Communication 16 Bit resolution (.1Hz)
(Digital Speed Reference)
Analog Outputs
One Isolated, Eight Non-isolated,
4…20 mA or 0…10V (600 Ω)
Communication Interface
Ethernet IP/DPI
Scan Time
Internal DPI – 2 ms min., 4 ms max.
Communications Protocols
(Optional)
DeviceNet
ControlNet
Ethernet I/P
Lon Works
Dual-port Ethernet I/P
Can Open
Profibus
RS485 HVAC
Modbus
RS485 DF1
Interbus
RS232 DF1
USB
Enclosure
NEMA 1 (standard)
IP21 (IEC)
NEMA 12 (optional)
IP42 (IEC)
Lifting Device
Standard / Removable
Mounting Arrangement
Mounting Sill Channels
Structure Finish
Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking
Key provision for customer input Disconnecting Device
Corrosion Protection
Unpainted Parts (Zinc Plated / Bronze Chromate)
Ambient Temperature
0…40 °C (32…104 °F) / 0…50 °C (32…122 °F) - optional
Fiber Optic Interface
Rectifier – Inverter – Cabinet (Warning / Trip)
Door Filter
Painted Defuser with Matted Filter Media
Table 1 - General Design Specifications (Continued)
Description