Chapter 1

Overview of Drive

Benefits of the 7000L “C” Frame Liquid-cooled Drive:

Completely integrated MV drive package reduces customer installation
costs and start-up time.

Higher power rating capability (up to 9000 hp / 6715 kW)

18 Pulse and AFE rectifiers for low harmonic solutions that meet IEEE
519-1992 Harmonic Guidelines

Motor friendly current and voltage output waveforms for use with
standard new and existing motors

Inverter duty motors not required

Motor temperature derating not required

No additional dv/dt or peak voltage stress to motor insulation system

Tested up to 15 kilometers (9.3 miles) cable distance between drive and
motor

Spacious cable termination cabinet for ease of use by installation
contractor

Cable termination stabs accommodate:

3 cables in / 3 cables out (Direct-to-Drive or AFE rectifier)

9 cables in / 3 cables out (18 Pulse)

Top or bottom entry and exit of line and load cables

90% of drive losses are rejected outside the control room

Integral liquid-cooled DC link inductor reduces overall dimension and
eliminates external interwiring.

Integral pumping panel includes:

Line supply c/w disconnect and fusing

Closed loop coolant system

Iron and chloride free liquid ethyl-glycol / deionized water mixture

Low conductivity coolant (1-2 micro-Siemens / cm

3

)

Isolated from medium voltage

Fully serviceable low voltage compartment isolated from medium
voltage power

Monitors coolant temperature, flow, level, conductivity, and pressure

Redundant pumping system (optional)

Automatic pump change over on pump failure

1/2 turn valves with quick disconnect couplers for pump replacement
when drive is operating

Full drip tray to contain any spilled coolant

Drain and fill pump for convenient filling

Industrial schedule 80 CPVC piping for pump panel, headers and
manifolds (no condensation possibility)

Control hardware for cycling of main / redundant cooling pumps and
heat exchanger fans

• “Plug and play” Power Cage concept

Central location for easy access to all main power components