Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 16

16
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
Chapter 1
Overview of Drive
Benefits of the 7000L “C” Frame Liquid-cooled Drive:
•
Completely integrated MV drive package reduces customer installation
costs and start-up time.
•
Higher power rating capability (up to 9000 hp / 6715 kW)
•
18 Pulse and AFE rectifiers for low harmonic solutions that meet IEEE
519-1992 Harmonic Guidelines
•
Motor friendly current and voltage output waveforms for use with
standard new and existing motors
–
Inverter duty motors not required
–
Motor temperature derating not required
–
No additional dv/dt or peak voltage stress to motor insulation system
–
Tested up to 15 kilometers (9.3 miles) cable distance between drive and
motor
•
Spacious cable termination cabinet for ease of use by installation
contractor
•
Cable termination stabs accommodate:
–
3 cables in / 3 cables out (Direct-to-Drive or AFE rectifier)
–
9 cables in / 3 cables out (18 Pulse)
–
Top or bottom entry and exit of line and load cables
•
90% of drive losses are rejected outside the control room
•
Integral liquid-cooled DC link inductor reduces overall dimension and
eliminates external interwiring.
•
Integral pumping panel includes:
–
Line supply c/w disconnect and fusing
–
Closed loop coolant system
–
Iron and chloride free liquid ethyl-glycol / deionized water mixture
–
Low conductivity coolant (1-2 micro-Siemens / cm
3
)
–
Isolated from medium voltage
–
Fully serviceable low voltage compartment isolated from medium
voltage power
–
Monitors coolant temperature, flow, level, conductivity, and pressure
–
Redundant pumping system (optional)
–
Automatic pump change over on pump failure
–
1/2 turn valves with quick disconnect couplers for pump replacement
when drive is operating
–
Full drip tray to contain any spilled coolant
–
Drain and fill pump for convenient filling
–
Industrial schedule 80 CPVC piping for pump panel, headers and
manifolds (no condensation possibility)
–
Control hardware for cycling of main / redundant cooling pumps and
heat exchanger fans
• “Plug and play” Power Cage concept
–
Central location for easy access to all main power components