Chapter 4

Commissioning

Capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.

Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.

Save the worksheet as “Drift @ 15 Degree Lead Angle”, for example.

Table 18 - Oscilloscope Setting

Figure 218 - Sample Waveforms

Synchronous Transfer Test to verify Sync Lead Angle (50Hz System)
Ch1: Idc1 (yellow), Ch2: Vuv (blue), Ch3: Vuvs (red)

While performing a live synchronous transfer:

Capture motor voltage at ACB test point “Vuv” & bypass voltage at ACB
test point “Vuvs”.

Capture and trigger on falling edge of the DC Link current waveform at
ACB test point “Idc1”.

Label the waveforms as “Vuv”, “Vuvs” and “Idc1”.

Save the worksheet as “Synch on Motor 01”, for example.

Table 19 - Oscilloscope Setting

Oscilloscope

Time Base

Waveform

Test-Point

Waveform Label

Ch. 1

10ms/div.

DC Link Current

Idc1

Idc1

Ch. 2

Motor Voltage

Vuv

Vuv

Ch. 3

Bypass Line Voltage

Vuvs

Vuvs

Oscilloscope

Time Base

Waveform

Test-Point

Waveform Label

Ch. 1

10ms/div.

DC Link Current

Idc1

Idc1

Ch. 2

Motor Voltage

Vuv

Vuv

Ch. 3

Bypass Line Voltage

Vuvs

Vuvs