Operator Interface

Chapter 3

Figure 123 - AC O/V, Disabled

Figure 124 - Fault Overview, Enabled

The state of the fault masks which you are currently viewing is defined to the
right of the screen name, i.e. FAULTS OVERVIEW: DISABLED or FAULTS
OVERVIEW: ENABLED. To change the state of fault masks currently displayed,
press the [F7]. Each press of the [F7] key will toggle the screen to show the masks in
the other state.

To change the state of a mask on the FAULTS OVERVIEW screen, use the
[cursor up] and [cursor down] keys to select the desired mask and press the
[enter] key. In the example of

Figure 123

, the “AC O/V” is currently disabled and

is selected. When [enter] is pressed its mask is enabled, thus removing the fault
from this screen as shown in

Figure 125

. Pressing [F7] toggles the screen to show

the enabled faults, which the AC O/V is one of (

Figure 126

). (If nothing

happens, you do not have proper access to the drive. Exit to the SETUP screen
and refer to the section entitled

Enter/Modify an Access Level on page 116

to

gain access).