Component Definition and Maintenance

Chapter 5

Figure 308 - Null-modem pin out

PowerFlex 7000 in Download Mode

To place the drive in download mode, you should be in the UTILITY –
TRANSFER screen. You will not be able to do this if the drive is running.
Ensure the drive is stopped, and the E-Stop is pressed. This is just a precaution, as
all versions of firmware 7.xxx and later will not allow you to attempt a download
while running.

Figure 309 - Current Access: Advanced

This time press F9 for SYSTEM, and a screen will appear telling you that you are
in download mode, and to recycle control power once the download is complete.

There are two status LEDs (D9 and D11) on the DPM, which provides
indication of the programming process. The following illustrates the states of the
LED: