beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 378

background image

378

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 5

Component Definition and Maintenance

• Solid Green

– when both LEDs are solid green, the Application firmware

is running.

• Flashing Green

– when either D9 or both LEDs are flashing, the board is

in download mode. (If the DPM bootcode is ≥ 1.005, then only D9 will
be flashing and D11 will stay solid. But if the bootcode is ≤ 1.005, then
both LEDs will be flashing.)

After putting the drive in download mode, the following is the display on the
drive terminal:

Figure 310 - System in Download Mode

If you press any Key after this message the PanelView will show “Communication
Error”.

Connect your PC to the DPM data port J4. Locate the PowerFlex 7000 Medium
Voltage Drive firmware file “PF7KFirmware7001_G.exe” and double-click to
download the file.