Figure 247 – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 300

background image

300

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 5

Component Definition and Maintenance

Figure 247 - Flow Restrictor Clamp

Also required are two (2) pieces of 3/8" hose (included) in spare parts kit
and four (4) M10 bolts with a length from 10 to 30 mm for use as plugs in
the 3/8" hose (not included). See

Figure 248

. M10 bolts must be clean.

Figure 248 - Flow Stopper for Servicing (2 required)

6.

Insert the 2 clamps per

Figure 249

on the 3/4-inch (19-mm) silicon hoses

to isolate flow between the vertical manifolds and the horizontal
manifolds of the converter modules.