System drain, Low voltage control section – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 344

background image

344

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 5

Component Definition and Maintenance

removing connections, as there will definitely be liquid leaking out. Use
absorbent pads or containers to catch the liquid.

System Drain

Turn off the pumping system and disconnect the switch on the cabinet door.
Attach the transfer pump to Drain/Fill line. Ensure that the flow arrow on pump
is in the correct direction. Open valve V6 and V7 (if provided) to pump coolant
out.

Low Voltage Control Section

The low voltage control section panel houses all of the control circuit boards,
relays, Operator Interface Terminal, DC/DC power supply, and most other low
voltage control components. Refer to

Figure 286

for a generic representation of a

low voltage tub arrangement.

Figure 286 - Low Voltage Compartment

Fiber Optic
Interface
Boards

DC/DC
Power
Supply

Analog

Control

Board

Tach Feedback

Circuit Board

Drive Processor

Module (DPM)

ANALOG

CONTROL

BOARD