Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

227

Commissioning

Chapter 4

Publication 1503-IN050_-EN-P, OEM Starter Frame and Components •
Installation Manual

Publication 1502-UM050_-EN-P, Medium Voltage Contactor, Bulletin
1502, 400 Amp (Series D) • User Manual

Publication 1502-UM052_-EN-P, Medium Voltage Contactor, Bulletin
1502, 400 Amp (Series E) • User Manual

Publication 1502-UM051_-EN-P, Medium Voltage Contactor, Bulletin
1502, 800 Amp • User Manual

If the Medium Voltage contactors or circuit breakers perform as desired, stop the
drive and perform the same test while operating in remote control.

Start the drive again and verify that all emergency stops installed in the system
function as desired. Ensure that all electrical interlocks installed in the system
function as desired. Make any necessary control wiring modifications at this time
and re-test the system if necessary.

Status Indicators

Drive status is often feedback to a plant’s process control either digitally through
the PLC input/output feature (see Chapter 3 – Operator Interface, PLC page 3-
43) or through relay logic. The following relays are provided with the drive as
standard:

It is necessary to activate each status indicator used by the customer to ensure that
they have connected their control to the drive correctly. This can be achieved by
changing the drive status (ready, faulted, warning etc.).

Analog I/O

It is possible to configure all of the drive’s analog inputs and outputs without
running the motor. The following information describes how to set up the
following drive features:

Analog Inputs

Analog Reference Command Input Scaling (Local, Remote)

Minimum Setting

Maximum Setting

Digital Reference Command Input Scaling (Digital)

Analog Outputs

Relay Name

Relay Designation

Run Contact

RUN

Fault Contact

FLT

Warning Contact

WRN

Ready Contact

RDY