Example:

The resistance across the anode-to-cathode of a 1500 amp device may be 57 kΩ
even though the sharing resistor is 80 kΩ.

A failure of an SGCT can be detected by measuring a lower than normal
resistance value; one device in the converter may read 15 kΩ whereas the rest of
the devices in the converter measured close to 60 kΩ. This indicates a partially
shorted device. A fully shorted device will read closer to 0 Ω and will be quickly
identified. If the SGCT is found to be out of tolerance, refer to

Component

Definition and Maintenance on page 265 (Chapter 5)

for detailed instructions

on how to replace the SGCT assembly.

Damage to a sharing resistor is easily detected if the SGCT is replaced and the
anode-to-cathode resistance remains abnormal. If the resistor is found to be out
of tolerance, refer to

Component Definition and Maintenance on page 265

(Chapter 5)

for detailed instructions on how to replace the snubber/sharing

resistor assembly.

Snubber Resistance (SGCT Device)

Access to the snubber resistor is not required to test the resistance. The snubber
circuit test point is located within the PowerCage under the chill blocks. For each
device, there is one test point. To verify the resistance, measure the resistance
between the test point and the chill block directly above the test point.

Figure 183 - Snubber Resistor Test

Refer to

Table 6

to determine the appropriate snubber resistance value for the

SGCT used in either the AFE Rectifier or the inverter.

If the resistor is found to be out of tolerance, refer to

Component Definition and

Maintenance on page 265 (Chapter 5)

for detailed instructions on how to

replace the snubber resistor assembly.

Measure resistance
between chill block
and test point.

Snubber Test Point

Measure resistance
between chill block
and test point.