Page 206

background image

206

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 4

Commissioning

Figure 190 - Snubber Capacitance Test

To test the snubber capacitance, disconnect the plug of the self-powered gate
driver board labeled SHARING and SNUBBER. The resistance between the
white wire of the plug and the Test Point to its left is the snubber capacitance.

Refer to

Table 7

to determine the appropriate snubber capacitance value for the

current rating of the SCR used. You should read the actual snubber capacitor
value shown in the table.

If the capacitor is found to be out of tolerance, refer to

Component Definition

and Maintenance on page 265 (Chapter 5)

for detailed instructions on how to

replace the snubber capacitor.

Control Power Tests

Although there are a variety of options available to customers that will effect the
control power distribution within the drive, the input will always be as illustrated
in

Figure 191

.

Snubber Test Point

White wire at
2-pole connector

Snubber Test Point

White wire at
2-pole connector

IMPORTANT

Prior to energizing the drive, verify that the control power being fed into the
input breakers is rated as designated on the electrical diagram.