Message prompting – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 134

background image

134

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 3

Operator Interface

Message Prompting

All the changes you made while you were configuring the drive are stored in
volatile memory of the drive. This means that when power to the drive is lost, so
will be the changes. To permanently store the changes, the contents of the
memory must be stored to NVRAM memory.

When you exit a group of screens on which you have changed the drive data, you
will be prompted as in

Figure 133

to save the data. If you wish to save the data,

press [F8] 'Yes' and the NVRAM screen (refer to

Store/Retrieve Configuration

(NVRAM) on page 135

) will be entered (

Figure 134

). If you wish the data to

reside as temporary data in RAM only, press [F9] 'No'. Pressing [F10] Exit will
return you to the screen from which you previously exited.

Note that the data can still be saved at a later time by accessing the NVRAM
screen directly from the Top Level Menu. Refer to

Store/Retrieve Configuration

(NVRAM) on page 135

.

Figure 133 - Message Prompt Screen

Figure 134 - NVRAM Screen