Application of medium voltage, Input phasing check, Application of medium voltage input phasing check – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 233
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
233
Commissioning
Chapter 4
Application of Medium Voltage
Before running the drive on Medium Voltage, it is a good idea to set up the
diagnostic trending feature to capture any information in the event of a fault
during commissioning. REMEMBER TO RESET THE TRENDING
BEFORE LEAVING THE DRIVE IN PRODUCTION.
The diagnostic trending operation of the drive allows you to capture the
relationships of 8 parameters over a period of time. Trending is a valuable tool for
trouble shooting the drive.
Refer to
for instructions on setting up the Diagnostic Trending.
The next test required to test phase rotation requires that medium voltage be
applied to the drive input. Ensure that the drive is thoroughly inspected for debris
and tools prior to energizing the drive. Furthermore, ensure that all protective
barriers have been re-installed before continuing. Ensure that you have taken the
drive out of System Test mode, and have returned to Normal operating mode.
Input Phasing Check
There are 9 voltage test points on the ACB board that will allow you to look at
each voltage level individually.
These test points are labeled as follows:
Table 12 - ACB Test Points and Associated Voltage Signals
All of these test points can be measured to either the Analog Ground (AGND)
on the board or the TE ground in the low voltage section. You can use V2uv as
your reference (trigger on this waveform) and verify all the other test points using
the table above. It is easier to use zero crossings on your oscilloscope as the
reference points when checking the phase shifts.
Essentially, you are verifying the following relationships:
Test Point Description
Isolation Transformer: Secondary Phasing
and Bridge
Phase Relationship with
respect to V2uv (2U)
V2uv
2U
Master
0°
V2vw
2V
Master
-120°
V2wu
2W
Master
-240°
V3uv
3U
Slave 1
-20°
V3vw
3V
Slave 1
-140°
V3wu
3W
Slave 1
-260°
V4uv
4U
Slave 2
+20°
V4vw
4V
Slave 2
-100°
V4wu
4W
Slave 2
-220°