Chapter 5

Component Definition and Maintenance

16.

Apply a 60Hz, 33% duty cycle signal to the OP1 fiber optic input.

17.

Verify that the diagnostics transmitter LED, OT1, is on.

18.

Verify that the signals at TP9 and TP8 are as shown in

Figure 260

.

19.

Verify that the signal between TP1 and TP2 is as shown in

Figure 261

and

Figure 262

.

20.

Remove the jumper between TB3-1 and TB3-2.

21.

Apply a constant fiber optic signal to the OP1 input.

22.

Apply a 60 Hz, 33% duty cycle signal, at a 0 to +2V level, between the
TB1-2 input and COM. Verify the signals in

Figure 263

and

Figure 264

.

Note that in

Figure 264

there should be a 220 μS, ±20 μS time between the

rising edge of the U4-pin7 pulse and the falling edge of the TP7 signal.

Figure 260 - Gating pulses