Chapter 4

Commissioning

Figure 198 - Cooling Cabinet Overview showing Valve Locations – 2

System Fill and Air Venting

1.

Attach transfer pump to drain/fill line (see drain/fill pump in

Figure 2

).

Ensure flow arrow on pump is in correct direction.

Figure 199 - Drain/Fill Pump

V11

V4

Pump 1

Pump 2

V5

V12

V3

V1

WARNING: Do not allow main pumps P1 and P2 to turn when dry. Damage to
seals can result.

Flow Direction

Transfer Pump