Control power components, Ride-through – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual
Page 321
![background image](/manuals/580441/321/background.png)
Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014
321
Component Definition and Maintenance
Chapter 5
Control Power Components
There are two configurations in which control power will be distributed for the
drive. The different methods are dependent on what drive option the customer
has chosen:
1.
)
2.
Remote Transformer and Starter (refer to
Ride-Through
Standard controls with 5 cycle ride-through
– The drive main control boards
will remain energized for a total of 5 cycles after control power is interrupted. If
control power is not restored during the 5 cycles, a controlled shutdown will
occur.
illustrates the control power distribution for 6-pulse and PWM drives
with integral starter/line reactor.
Figure 267 - AFE Line Reactor Drives
illustrates the control power distribution for 6-pulse and AFE drives
with remote transformer/starter or integrated line reactor with remote starter.
-Printer
-Operator Interface
-Relays
DC/DC CONVERTER
VFD
AC/DC Converter
56V DC
100 0W/150 0W
+5V-LOGIC
+/-15V-LOGIC
+/-24V-HECS
+24V-ISOLATORS
+24- XIO
SENSE CABLE
20V
C Hold-up
Fan
20V Isolated
Gate Driver
Power Supp ly
380V 50Hz
or
460V 60Hz
3-ph
DC Fail
Line
Reactor
Line
Filter
Customer
Supp lier
120V
1-ph