Drive Installation

Removal of DC Link Choke Turnbuckle Supports

Remove turnbuckles which attach choke to top lifting angle pair as follows:

Remove cotter pins (see

Figure 43

) from bottom turnbuckle jaw then top.

Carefully remove turnbuckles. Retain for future use.

Figure 43 - Choke Cabinet

Re-install any capacitors that were removed.

Proceed with Removal of Lifting Angles.

Removal of Lifting Angles

Lifting angles should be removed only when the Drive is in its final location. The
lifting angles are retained with 5/8"-11 hardware. The 5/8" bolts need to be re-
installed in their holes in the top of the Drive to prevent the ingress of foreign
matter into the enclosures. See

Figure 44

.

Remove cotter pins