Component Definition and Maintenance

Chapter 5

13.

Press F4 [RATE] key. The cursor moves to the rate field. Here we will
enter 0, which is the fastest sample rate (1 msec/sample) and then press
Enter

key.

Figure 326 - Rate Option

14.

Press F5 [POST] key and enter 10 (this is the percentage of post-trigger
samples) and then press the Enter key.

Figure 327 - Post Option

15.

Now, press F10 [EXIT] key to exit to ‘Diagnostic’ screen. On the
‘Diagnostics’ screen, verify that the Status is ‘Running”, which means the
Diagnostic Trend is ready and will capture the data whenever the trigger
condition is satisfied. If the Status shows ‘Stopped’ then press F7 [Re-Arm]
key. This will change the Status to Running.