beautypg.com

Equipment needed, Procedure, Equipment needed: procedure – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 313

background image

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

313

Component Definition and Maintenance

Chapter 5

TB3-3

– Common connection of positive 15V power supply used for test power

TB4-2

– Cathode connection to SCR being controlled

TB4-1

– Gate connection to SCR being controlled

OP1

– Blue fiber optic cable receptacle – Firing pulse command from the

processor

OT1

– Grey fiber optic cable receptacle – Diagnostic status of the SCR

Testing procedure for SCR
self-powered gate driver
board

Equipment needed:

Digital oscilloscope

Function generator w/duty cycle control

DC power supply (+15V @ 300 mA required)

Digital multimeter

Temperature sensor board (80190-639-02)

Procedure:

1.

Connect a clamped ABB #5STP03D6500 SCR to the gate-cathode leads
of the SPGDB board (TB4-1/TB4-2).

2.

Attach a temperature sensor board to the TB2-1/TB2-2 terminals.

3.

Apply +15V test power to terminals TB3-1 and TB3-3 (TB3-1 is at +15V
while TB3-3 is the +15V return). Leave TB3-2 open.

4.

Measure TP4 to TP3, which should be +14.4V, ±100mV.

5.

Measure TP5 to TP3, which should be +5.0V, ±250mV.

6.

Measure TB2-1 to TB2-2, which should be +14.4V, ±100mV.

7.

Measure the voltage at U4-pin2 to COM, which should be +1.0V,
±100mV.

8.

Measure the voltage at U4-pin3 to COM, which should be 0V.

9.

Measure the voltage at U4-pin7 to COM, which should be +3.6V,
±100mV.

10.

Verify that the OT1 LED is off.

11.

Measure TP7 to TP3, which should be 0V.

12.

Measure TP9 to TP3, which should be +5.0V, ± 250mV.

13.

Measure TP8 to TP3, which should be 0V.

14.

Measure TP1 to TP2, which should be 0V.

15.

Connect a jumper between TB3-1 and TB3-2 and verify that the voltage