beautypg.com

Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C-Frame) - ForGe Control User Manual

Page 82

background image

82

Rockwell Automation Publication 7000L-UM301D-EN-P - June 2014

Chapter 2

Drive Installation

Figure 66 - Pipe Flange Detail

Table 5 - Customer Cooling Requirements for Liquid-to-Liquid Heat Exchangers

Process Water Inlet

Drive Coolant Outlet

1.25 in. or 2.0 in. NPTF
Female Pipe Threads

Process Water Outlet

Drive Coolant Inlet

Drive

Min. Flow Rate

Max. Pressure

(psig)

Pressure Drop

(kPa)

Temperature (°C)

Rectifier

Voltage

Amps

US Gpm

(1)

L/m

(2)

Min.

Max.

18 Pulse

4160

375

19.5

72

435

7

> 0

<32

430

21.5

80

435

8

> 0

<32

495

26.5

100

435

13

> 0

<32

575

29.0

109

435

15

> 0

<32

657

37.5

142

435

25

> 0

<32

6600

375

33.0

125

435

18

> 0

<32

430

44.5

167

435

34

> 0

<32

495

48.5

184

435

40

> 0

<32

575

54.5

206

435

43

> 0

<32

657

62.6

237

435

49

> 0

<32

AFE

4160

375

19.5

74

435

7

> 0

<32

430

24.0

90

435

10

> 0

<32

495

26.5

100

435

13

> 0

<32

575

33.0

125

435

19

> 0

<32

6600

375

37.0

139

435

24

> 0

<32

430

44.5

167

435

34

> 0

<32

495

48.5

184

435

40

> 0

<32

575

54.5

206

435

43

> 0

<32

(1) US Gpm = Gallons per minute (U.S.)
(2) L/m = Liters per minute