beautypg.com

Rs-232 report function, Compact report, Starting date – Teledyne 6200E - Sulfides Analyzer User Manual

Page 134

background image

Operating Instructions

Model 6200E Instruction Manual

134

M6200E Rev: A1

6.11.2.7. RS-232 Report Function

The M6200E iDAS can automatically report data to the communications ports, where they can be
captured with a terminal emulation program or simply viewed by the user.

To enable automatic COM port reporting, follow the instruction shown in section 6.11.2.2 then
press

:


Edit Data Channel Menu

From the DATA ACQUISITION menu

SETUP X.X

0) CONC: ATIMER, 2, 4032, R


PREV NEXT INS DEL

EDIT

PRNT

EXIT

Exits to the main

Data Acquisition

menu

SETUP X.X

NAME:CONC


SET>

EDIT

PRINT

EXIT

SETUP X.X

RS-232 REPORT: OFF


EDIT

PRINT

EXIT

ENTR accepts the new

setting and returns to the

previous menu.

EXIT ignores the new setting

and returns to the previous

menu.

SETUP X.X

RS-232 REPORT: OFF

OFF

ENTR EXIT

Toggle key to turn

reporting ON or OFF

Press SET> key until…

6.11.2.8. Compact Report

When enabled, this option avoids unnecessary line breaks on all RS-232 reports. Instead of
reporting each parameter in one channel on a separate line, up to five parameters are reported in

one line, instead.

6.11.2.9. Starting Date

This option allows to specify a starting date for any given channel in case the user wants to start

data acquisition only after a certain time and date. If the Starting Date is in the past, the iDAS
ignores this setting.