522

Vess R2000 Series Product Manual

Promise Technologies

S

huttIng

D

own

the

S

uBSySteM

(clu)

There are two methods for shutting down the subsystem. Choose one of the following procedures:

“Shutting down the enclosure – Telnet Connection” on page 522

“Shutting down the enclosure– Serial Connection” on page 524

s

huttiNg

dowN

the

eNClosure

– t

elNet

C

oNNeCtioN

This function shuts down the Vess R2000 subsystem on a Telnet connection. Additional action is required, as

described below.

Important

If you have a JBOD Expansion, always power off the RAID subsystem first.

Then power off the JBOD subsystems.

To shutdown the RAID subsystem:

1. From the Main Menu, highlight

Additional Info and Management

and press

Enter

.

2. Highlight

Shutdown or Restart

and press

Enter

.

3. Highlight

Option

and press the spacebar to display

Shutdown

.

4. Highlight

Submit

and press

Enter

.

A warning message appears.

5. Press Y to continue.

The screen goes blank.

6. Wait for no less than two minutes.

7. The subsystem will then turn off the system power one after another.