WebPAM PROe - System Configuration

M

akiNg

ups s

ettiNgs

These settings control how the Vess R2600 subsystem detects the UPS unit and responds to data reported by

the UPS unit.

To make UPS settings:

1. Click the

Device

tab.

2. Click the

UPS

icon.

3. Click the

UPS Settings

button.

4. Perform the following actions as required:

• Verify the Current UPS Communication method. See Note 1:

SNMP

– Network connection.

USB

Unknown

– No connection.

• Choose a Detection Setting from the drop-down menu:

Automatic

– Default. If a UPS is detected when the subsystem boots, the settings

changes to Enable.

Enable

– Monitors UPS. Settings changes, reports warnings, and logs events.

Disable

– Does not monitor UPS.

• Type values into the Threshold fields. See Note 2:

Running Time Remaining Threshold

– Actual time below this value resets

adaptive writeback cache to writethrough.

Warning Temperature Threshold

– Actual temperature above this value triggers a

warning and logs an event.

Loading Ratio Threshold

– Actual loading ratio (percentage) above this threshold

triggers a warning and logs an event. See Note 3.

• For UPS units with network cards, type the IP addresses or

DNS names in fields UPS 1 and UPS 2. See Note 4.

5. Press

Submit

to save your settings.

Note 1: Vess R2600 supports multiple UPS units using network or USB connections, but not a combination