Chapter 1 Specifications Check

33

1.8 Noise Elimination and Mounting Method

(1) Noise Elimination Grounding (Frame Ground)

(2) Precautions regarding wiring method

1) Wire is to be twisted for the power supply.

2) Separate the signal and encoder lines from the power supply and power lines.

(3) Noise Sources and Elimination

Carry out noise elimination measures for electrical devices on

the same power path and in the same equipment.

The following are examples of measures to eliminate noise

sources.

1) AC solenoid valves, magnet switches and relays

[Measure] Install a Surge absorber parallel with the coil.

2) DC solenoid valves, magnet switches and relays

[Measure] Mount the windings and diodes in parallel.

Select a diode built-in type for the DC relay.

Earth Terminal

Class D grounding

(Formerly Class-III grounding :

Grounding resistance at 100: or less)

Copper wire: Connect a ground

wire with a diameter of 1.6 mm

(2mm

2

: AWG14) or larger.

Connect the ground line to

the FG terminal block on the

controller unit.

Controller

Do not share the ground wire with or connect

to other equipment. Ground each controller.

Controller

Other

equipment

Controller

Other

equipment

Other

equipment

Surge absorber

Relay

coil

Relay coil

R

C

+24V

0V

+24V

0V

+

-